RETIRED - SRL2K7 - Infrared Refrigerant Leak Detector

Infrared Refrigerant Leak Detector for HVACR - Superior Sensitivity in a Rugged Design for HVACR
Like all of Fieldpiece's test instruments, the SRL2 Infrared Refrigerant Leak Detector is designed exclusively to make the HVACR Technician's job easier, faster, safer and more efficient. We set out to develop the best refrigerant leak detector for HVACR. We believe the SRL2 is it. It comes in kit form in a rugged, blow-mold case with all of the extras (see What's Included tab).

The ergonomic design fits naturally in your hand. The ruggedized construction stands up to abuse most other leak detectors can't handle. The eight-hour battery life lets you work all day before recharging and the included vehicle and wall chargers help you during overtime. The mute and peak functions allow you to work the way you want to work. The magnetic hanger helps keep the detector out of the way when repairing a leak, but visible enough so you won't leave it on the job.

Advantages Over Other Types of Refrigerant Leak Detectors  

  • Triggers on all CFCs, HFCs, HCFCs and blends.
  • Sealed sensor. Unlike heated diode and corona discharge leak detectors, the sensor doesn't "touch" refrigerant as it passes through the instrument. Heated diode and corona   discharge units tend to degrade or fail when they come in contact with high concentrations of refrigerant or touch liquid.
  • Doesn't trigger on oil or moisture like other types of detectors.
  • Senses change in refrigerant levels. Works even in contaminated environments.
  • Up and running in less than 30 seconds. Some heated elements and corona discharge units take much longer to warm up. UV dyes can take several hours to travel through a running system and can degrade system components.

Designed for HVAC-R

  • Superior - Controlled Sensitivity. Doesn't trigger on nuisance leaks unless in Turbo Mode.
  • Rugged / Ergonomic Features. Ruggedized boot and it fit's in your hand.
  • Infrared Sensor. Lasts up to 10 years.
  • Three Sensitivity Levels. Plus Turbo Sensing Mode - Meets SAE standards.
  • Audible/Visual Alarm. Turn the beep on or off - you decide.
  • 8-hour Battery Charge. Work all day on one charge.
  • Non-conductive, Sturdy Probe. Stays where you want it.
  • Peak / Mute Buttons. Find leaks in noisy environments.
  • Magnetic Hanger. Hang the unit while you repair the leak.
  • Weighs 14-oz. Tough doesn't have to mean heavy.

 

REFRIGERANT CLASS INFORMATION

 

(SRL2K7)

 

WHAT'S INCLUDED

  • Advanced Refrigerant Leak Detector - SRL2(K7)
  • (5) O-rings and 10 Replacement Filters - RFL2
  • 9-inch Flex-Probe Extension - RFE2
  • Rigid Extension Probe - RRE2
  • Blow-Molded Case - ABMK3
  • Operator’s Manual
Specifications
Sensing element: Enhanced infrared photo optics 
Sensor life: 10 years
Refrigerants: HFC, CFC, HCFC, and blends
Sensitivity: Min (Stationary): 0.1oz/yr (3g/yr) Max (Stationary): >1.05oz/yr (>30g/yr) Min (In motion): 0.18oz/yr (5g/yr) Max (In motion): >1.05oz/yr (>30 g/yr) After exposure to (50g/yr): 0.1 oz/yr (3g/yr) In poluted environment: 0.1 oz/yr (3g/yr)
Response time: 1 second Recovery time: ~4 seconds Auto off: 10 minutes after no activity
Battery: 3.7VDC(nominal), rechargeable lithium ion user-replaceable battery.
Battery life: 8 hours continuous use prior to needing a charge. Degradation (30%) after 500 charge/discharge cycles or two years, whichever comes first.
Low battery LED: Lights when approximately 1 hour of battery life remains.
Charge time: Less than 4 hours (either charger)
Operating environment: 32ºF (0°C) to 104ºF (40°C) at <75%RH (non-condensing)
Storage environment: <80%RH meter and batt. For 80% battery recovery: -4ºF (-20°C) to 140ºF (60°C) less than 1 month -4ºF (-20°C) to 113ºF (45°C) less than 3 months -4ºF (-20°C) to 68ºF (20°C) less than 1 year

SKU SRL2K7
Brand Fieldpiece
Shipping Weight 1.5000kg
Shipping Width 0.400m
Shipping Height 0.300m
Shipping Length 0.150m
Shipping Cubic 0.018000000m3
Unit Of Measure ea
1 - Year from Date of Purchase
​Excludes Consumables such as Filters, Gaskets, Leads, Batteries, Fuses, Sensors, Case etc

Be The First To Review This Product!


Help other FIELDPIECE AUSTRALIA visitors by writing reviews for products you have used or purchased.

Click here to write a product review


More From This Category


Multiple currency display

Retired Stock Clearance

HG2 System Analysers, Accessory Heads, Wireless handles

Contact Us, Call or Email us for details. USE CODE Word - "Clearance"